57-649 Jupiter Magnetostrictive Transmitter - FOUNDATION fieldbus™
23
5.1.2 Status Messages
Display Message Action Comment
OK None Normal operating mode
Initial None Shown at power-up during
self check
Default Cal Factory set default calibration parameters Consult Factory
are in use, level reading may be inaccurate
Lo Temp Present temperature in electronics Transmitter may need to be moved
compartment is below -40° C to ensure temperature is within
specification
Hi Temp Present temperature in electronics Transmitter may need to be moved
compartment is above +80° C to ensure temperature is within
specification
Float 2 No level signal detected from float 2 Make sure 2 floats are being used,
Fail are not damaged, and within
measuring range
Float 1 No level signal detected from float 1 Make sure float is not damaged
Fail and within measurement range
No Signal No signal detected from any float Make sure float is not damaged
and within measurement range
Snsr Brd Fail No signal from probe, bad board or Check electrical connections
connection problem to probe
DfltParm Internal non-volatile, parameters have Consult Factory
been defaulted